EA-13-118 · CAL · Issued 2013-08-23 · Reactor Licensees
Action
EA Number
EA-13-118
Licensee
NOV (White)
Category
Reactor Licensees
Action type
CAL
Date issued
2013-08-23
Description
On August 23, 2013, the NRC issued a Notice of Violation (NOV) to Tennessee Valley Authority for a violation of Technical Specification Section 5.4.1, Procedures, associated with a White Significance Determination Process finding involving the failure of Browns Ferry personnel to properly implement a procedure recommended in Regulatory Guide 1.33, Revision 2, Appendix A, dated February 1978. Specifically, on December 22, 2012, the licensee failed to properly implement the procedure for Startup, Operation, and Shutdown of the Reactor Protection System, 2-OI-99, Reactor Protection System, step 5.1[3], when an operator incorrectly opened the RPS motor generator set tie to battery board 2 Breaker on the A RPS bus motor generator set while attempting to start the B RPS bus motor generator set. The failure to properly implement 2-OI-99 caused a Unit 2 reactor SCRAM and MSIV closure.